GENERAL
- UPS Type: Rack / Tower
- Phase: 1 phase in / 1 phase out
- Rating (VA): 6000
- Nominal Power (W): 6000
- Standard Model Dimension (mm):
UPS Unit: 610 x 438 x 88 [2U] (D x W x H), Battery Pack: 600 x 438 x 133 [3U] (D x W x H)
- Weight (kg): UPS Unit: 17, Battery Pack: 57
INPUT
- Connection Type: Terminal
- Nominal Voltage: 208/220/230/240 VAC VAC
- Voltage Range: 110~300VAC ± 3% at 50% load, 176~300VAC ± 3% at 100% load
- Frequency Range: 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
- Power Factor: ≧0.99
- THDi: < 4% @100% Load, < 6% @50% Load
OUTPUT
- Connection Type: Terminal
- Nominal Voltage: 208*/220/230/240 VAC
- Voltage Regulation: ±1%
- Frequency Range (Synchronized Range): 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
- Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
- Current Crest Ratio: 3:1 (max.)
- Harmonic Distortion: ≦1% THD (Linear load), ≦4% THD (Non-linear load)
ALARM & INDICATORS
- Battery Mode: Sounding every 4 seconds
- Low Battery: Sounding every second
- Overload: Sounding twice every second
- Fault: Continuously sounding
- LCD: Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault
CONNECTIVITY, CONTROL & MONITORING
- Front panel: Status LED, Function keys, LCD display
- Communication: Smart RS232*, USB Port, Emergency Power Off (EPO)
BATTERY
- Standard Model Type: 12V / 7Ah
- Numbers: 20
- Typical Recharge Time: 9 hours recover to 90% capacity